The
ET-6000 is a web-based Ethernet I/O module. It has a built-in web
server that used for
all configuration and I/O data monitoring and controlling using a
regular web browser
dynamically. No extra programming tools or HTML editor are needed. Thus
users can
easily and safely access the ET-6000 from anywhere at and any time all
over the world.
In addition, the ET-6000 also supports various Modbus functions. For
example,
Modbus/TCP slave, Modbus/TCP to Modbus/RTU gateway, Modbus/RTU master,
Modbus/RTU slave, and etc, meaning the ET-6000 can easily be integrated
into any
SCADA software environment using the Modbus protocol.
The ET-6000 module is designed to be used in industrial monitoring and
measurement
applications, so the hardware has been manufactured to survive in harsh
and noisy
environment. As a result, the module contains 3-way isolation against
noise and surge
signals, has a wild range power input (10~30VDC) and can operating at
temperature
ranging from -25~+75 C.
Features
8 DO (Relay) and 10 DI
10/100 Mbps Ethernet
Modbus protocol support
Web browser configuration
Transmission status LED display
3-way isolation protection
Technical parameters
et-6060d
Product specification
CPU
CPU
80186 , 80MHz
SRAM
512
KB
Flash Memory
512
KB
EEPROM
16
KB
Dual Watchdog
Yes
Communication
Serial Port
RS-232
(TXD, RXD, GND) (115200 bps Max.)
Ethernet Port
10
/ 100 Base TX (With Link, Activity LED Indicator)
Small Man
Machine Interface
7 Segment LED Display
5
Digits
System LED Indicator
4
Push Button
4
Digital Output
Output
Channels
8
LED Indicator
Yes
Output Type
Power
Relay, Form A (Normal Open)
Operating
Voltage Range
5
~ 240VAC (47~63Hz)
5
~ 24VDC
Relay Contact
Voltage Range
0~ 250VAC (47~63Hz)
0~ 28VDC
Max.
Load Current
3.0 A/Channel
Max.
Operate Time
15 ms Max.
Max.
Release Time
3 ms Max.
Insulation
Resistance
Min. 1,000 MOhms, at 500VDC
Dielectric
Strength
Between
Open Contacts : 750VAC 50/60Hz (at 1 Minute)
Between
Coil and Contacts : 4,000VAC 50/60Hz (at 1 Minute)
Surge Strength
10,000V
(at 1.2*50us)
Relay Life
Mechanical
:10 million operations at no Load Condition